How do I perform a Factory Reset of an ATV340 drive via the keypad?

Published date: 11 February 2019

Issue:
Customer wants to reset the programming to factory default using the keypad of the drive.

Product Line:
ATV340 series

Environment:
All

Cause:
NA

Resolution:
From RDY, Press ENTER and scroll to CONF.
Press ENTER and scroll to FULL.
Press ENTER and scroll to FMt (Note that "M" appears as an upside down capital U.  We can not make an M with a 7 segment display)
Press ENTER and scroll to FCS-
Press Enter and scroll to FCS,
Press ENTER and scroll to INI.  Press AND HOLD enter for 4 seconds to perform factory reset of the drive programming.



 