Browse FAQs

How is undercurrent fault setup on the Tesys T?

Published date: 23 January 2019

Issue:
How is undercurrent fault setup on the Tesys T?

Product Line:
Tesys T

Environment:
All

Cause:
Fault detection.

Resolution:
Under Parameter List, Current submenu, set undercurrent fault to enable (disable is default).
Undercurrent fault threshold min 30% of FLC (Full load current) to 100% FLC.  Default is 50%.
Undercurrent fault timout has a range of 1 to 200s with default timeout period of 10s.
Undercurrent warning enabe allows undercurrent warning threshold to be programmed.  30 to 100%FLC as range and 50% FLC as default.

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.