Browse FAQs

What can cause an InFC or internal error 12 on the ATV630 and ATV930 Process drives?

Published date: 11 January 2019

Issue:
InFC or internal error 12 on the ATV630 and ATV930 Process drives

Product Line:
ATV630 and ATV930

Environment:
All 

Cause:
Internal current supply error 
- defect of the current transformer
- defect on the power supply on the inverter / AFE power board

Resolution:
This error could occur on S6, ATV•30F, ATV•50F, ATV•60 and ATV•80.
The InFC error is raised when the current sensor supply monitoring has detected
an low level on the current sensor supply.

- Check with SoMove service section, on which brick the fault occurs
Power OFF the drive and disconnect the current transformer of the identified brick,
Power ON the device and check if the fault raised again, if the fault is not present the current sensor is damaged - > change the brick.
If the fault raised again, change the inverter board or AFE brick power board of the identified Brick

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.