What can cause an InFA or internal error 10 on the ATV630 and ATV930 Process drives?

Published date: 09 August 2019

Issue:
InFA or internal error 10 on the ATV630 and ATV930 Process drives?

Product Line:
ATV630 and ATV930

Environment:
All 

Cause:
The external supply voltage is to high. 
The P24 voltage input for the customer 24vdc supply is monitored against 
overvoltage. The error raise at P24 > 30.5vdc

Resolution:
Check the external 24V supply make sure its less than 30.5vdc
 