Can we use SF / UTP AWG24 ethernet cable for ATV32, 320,340, ATV630 (embeded+advanced eth, ATV930 ?

Published date: 11 January 2019

YEs, it is possible, Ethernet cable corss-section does not need to be AWG22 min, it is enough to be AWG24 or any greater cross-section.
Recommendation is to keep SF/FTP type