How do I program an ATV340 to use the dial of drive as speed and DI1 terminal as start and stop control?

Published date: 26 July 2019

Issue:
Programming an ATV340 to use the dial of HMI for speed reference and digital input (DI1) for Start/Stop control

Product Line:
Altivar 340, ATV340

Environment:
All

Cause:
Programming setup

Resolution:
In the Main Menu, select Complete Settings, then Command and Reference.
Set [Ref Freq 1 Config] Fr1 to [Ref Freq-Rmt Term] AIV1
Set [Control Mode] CHCF = [Separate] SEP
Verify  [Cmd channel 1] CD1 = [Terminals] TER
 





 