What is the required control voltage for the ATS48?

Published date: 19 December 2018

Issue:
What is the required control voltage for the ATS48?

Product Line:
Altistart 48 Soft Starter 

Environment:
All

Cause:
Installation documentation

Resolution:
ATS48...Q the control circuit voltage is 220 - 15 % to 415 + 10 %, 50 / 60 Hz
ATS48..Y control circuit voltage is 110 - 15 % to 230 + 10 %, 50 / 60 Hz
This is AC voltage, and is applied to the CL1 and CL2 terminals.



 