What are the minimum mounting clearances for ATV660 Enclosed Drive Systems?

Published date: 18 December 2018

 Issue:
Looking to see if they can mount the ATV660 drives side by side and what other minimum clearances are required. 

Product line:
Altivar 660, ATV660, Enclosed Ativar Process System

Environment:
n/a

Cause:
Unable to find documentation of requirements.

Resolution:
In document NHA37111_03, dated 10/2017, page 27.  The onlny minimum clearances are 100mm (3.93 inches) or more on the top and 1000mm (39.37 inches) from the front.  These clearances are to facilitate proper airflow. 

There are no minimum clearances on the bottom, the back or the sides of the enclosure.  Mounting the enclosed drive systems back to back or side to side is permitted.