Can we use VW3A3502 multipump card on ATV71?

Published date: 17 December 2018

YEs, it is possible and we tested it. Do not forget to set parameters manually, profile = separated, reference from AI1, commands from CI card. And manually configure PI regulator (feedback on AI2, etc.)