Magelis HMI is showing Invalid ROM Section error

Published date: 13 December 2018

Issue: After every download of a project, the Magelis HMI is showing an Invalid ROM section error.

Cause: It is possible that a connection disruption during download can cause an invalid rom section on your Magelis HMI.

Product Range: XBTGT, XBTGK, HMISTU, HMISTO, HMIGTO, HMIGTU, HMIGK, XBTGH.

Resolution: In order to clear the Invalid ROM section, it is necessary to install the application by USB Memory stick or CF/SD card. This method performs a clean wipe before of the runtime firmware before installing the application.

 