What cable is used to connect at BMXNRP020x to a BMxCRA312x0 module?

Published date: 12 December 2018

Issue
What kind of cable is used to connect  a BMXNRP020x fiber module to a BMxCRA312x0 Drop module?

Product line
M580, X80

Resolution
The BMXNRP020x to a BMxCRA312x0 connection is a standard RJ45 copper Ethernet connection. The maximum distance is less than 100 m,using shielded twisted 4-pair CAT5e or greater (10/100 Mbps) cable. (We do not recommend using twisted 2-pair CAT5e or CAT6 cables.)

Typically a customer will use anything that they already have available to them, but attached is a list of available ConneXium cables. Any of the straight through will work.

 