Browse FAQs

What is an internal serial link fault (INF3) on an ATV320 drive?

Published date: 11 October 2018

Issue:
What is an internal serial link fault (INF3) on an ATV320 dirve?

Product Line:
Altivar 320

Environment:
All

Cause:
Communication interruption between internal cards of VFD

Resolution:
Check internal connections.  
If there is an option card, remove and re install.
Power cycle the VFD.  
Factory reset if needed.
Power up with no option card if instaled (this will perform factory reset)

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.