What can cause an INF2 or internal error 2 on the ATV630 and ATV930 Process drives?

Published date: 28 September 2018

Issue:
What can cause an INF2 or internal error 2 on the ATV630 and ATV930 Process drives?

Product Line:
ATV630 and ATV930 Process drives

Environment:
All 

Cause:
 The Powerboard was exchanged by a spare part, and is not configurated to the correct power rating.

Resolution:
Unknown or Incompatible Power Board
Principle
asdssadf
Probable causes 
• The Powerboard was exchanged by a spare part, and is not configurated to the correct power rating.
Remedies
• Switch OFF/ON the inverter.
• Check the reference number of the power board.
• connect to the SoMove service section and use the "drive type recovery function" to set a valid configuration of the power board.
• Replace the controlblock
 