ATV630 show PID feedback warning , how to get rid of the fault?

Published date: 24 September 2018

It is due to wrong limits for PID feedback monitoring.
If PFAH warning is displayed, it means that PID feedback has reached high threshold PAH [PID feedback high threshold]
Additionally if relay output has been assigned to PID feedback warning, it would be activated as well.
See extracted pages to fix high PID feedback warning. Increase PAH or lower PAL in order to alway have PID feedback in this area PAL-PAH