Browse FAQs

How to allow the ATV320 to drive up above 60 hz?

Published date: 20 September 2018

Issue:
How to allow the ATV320 to drive up above 60 hz?

Product Line:
Altivar 320

Environment:
All

Cause:
N/A

Resolution:
Go into CONF, FULL, SIM-, and set TFR to a value above 60 hz.
TFR is max frequency.
Next set HSP under SIM- menu to value desired to a max value of TFR.  
HSP -High speed can not be set higher than tFr -max frequency.


Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.