Concept v2.6 - is there an averaging block for an analog signal?

Published date: 07 September 2018

The AVGMV block could be used. It takes in a REAL input and allows the user to define the number of scans that will buffer before averaging. If the analog signal is not REAL, use standard conversion blocks such as W_INT_REAL and REAL_TO_WORD.

 