ODBC connection for Crystal Reports in ClearSCADA

Published date: 05 September 2018

ClearSCADA uses a native 64-bit Crystal Reports runtime and therefore requires a 64-bit ODBC system DSN configured.

Crystal Reports itself is a 32-bit program and needs a 32-bit ODBC system DSN configured.

For this reason, both a 32-bit system DSN and 64-bit system DSN need to be configured on the ClearSCADA server PC.  A user may use the following steps in order to configure both of these system DSN's:


1) Using Windows File Explorer, navigate to C:\Windows\System32 and locate the odbcad32.exe file.




2) Double-click to open the ODBC Data Source Administrator (64-bit).  Click on the 'System DSN' tab and then click the 'Add' button.  Select the 'ClearSCADA Driver'.



3) In the name field enter: ClearSCADA  Ensure the system is set to the local database (i.e. MAIN) and ensure 'Allow Anonymous' is checked.
    (Optional: fill out the 'User Name' and 'Password' fields.)



4) Click 'OK and 'OK' again to close these dialogs.



5) Now navigate to C:\Windows\SysWOW64 and locate the odbcad32.exe file.



6) Double-click to open the ODBC Data Source Administrator (32-bit)



7) Repeate steps 3) and 4)



8) No go into the ClearSCADA server configuration | Global Parameters | Crystal Reports dialog



9) Ensure the DSN field reads: ClearSCADA



It is important that the spelling of ClearSCADA is consistent in both system DSN's and in the server configuration.

Restart the ClearSCADA server in order to activate the connection.