Is the 2510F manual starter acceptable to OSHA as an energy isolation device suitable for lockout / tagout?

Published date: 05 September 2018

Issue:
Is the 2510F manual starter acceptable to OSHA as an energy isolation device suitable for lockout / tagout?


Product Line:
2510 Type F


Environment:
All models


Cause:
NA


Resolution:
These do not meet OSHA requirements for Lock Out/Tag Out. This product is a manual starter, not a disconnecting means.
 