Video: What is the part number of the Expansion module to be used with TeSys T motor controller?

Published date: 30 October 2018

Issue:
Understanding Differences Between TeSys T Extension Modules

Product Line:
TeSys T

Environment:
LTMR

Resolution:
The part numbers are LTMEV40BD and LTMEV40FM. The expansion modules add voltage measurement between phases up to 690V nominal and 4 additional inputs.  
  • LTMEV40BD: requires 24VDC input voltage with 4 inputs.
  • LTMEV40FM: requires 100-240VAC with 4 inputs.  

 