Is the BMENOC0301 module hot swappable?

Published date: 02 July 2019

Issue
Desire to replace the NOC without impacting the CPU.

Product line
Modicon M580

Resolution
The BMENOC0301 module can be replaced simply by removing the cables, lifting it out of the backplane then dropping the new one in and replacing the cables. It will receive the configuration from the M580 after booting up.

 