Technical FAQs

Ask a Question

ATV6xx, ATV9xx when monitoring LCr (motor current) over communications, what feedback would you expect?

Issue:
ATV600, ATV900 when monitoring LCr (motor current) over Communications, what feedback would you expect?

Product Line:
ATV
 
Environment:
All

 
Cause:
Communication

 
Resolution:
LCR unit: [A]
drives up to     ..D15           coeff.: 0.01
drives:     D18..  to ..C16     coeff.: 0.1 
drives higher than     C16..  coeff.: 1

 
Was this helpful?
What can we do to improve the information ?