ATV320 how to adjust directly the speed reference via the jog dial

Published date: 12 December 2018

Issue: 
How can I adjust the speed from the jog dial on the drive?
 
Product Line:
Altivar ATV  Process Drive
 
Environment:

ALL
 
Cause:

Programming Wiring


Resolution:
To do the same as ATV312 after pressing Mode key.

ConF > FULL > CtL > 
  Fr1 = A1U1
  CHCF = SEP (hold 2s)
  Cd1 = tEr
ESC back to RDY

You can now press Enter (Dial) 3x to adjust the speed