How does the points capacity allocate when routing function is implemented in BMXNOR0200

Question:
How does the points capacity allocate when routing function is implemented in BMXNOR0200?
 
Answer:
If customer is using routing function(forwarding function), the points counts should include both client side & sever side. So customer have to use half of capacity points(3500) at either client side or sever side.
 