Technical FAQs

Ask a Question

What is the ATV320 24Vdc input loading?

Issue:
What is the consumption on the ATV320 digital inputs? 

Product Line:
ATV320

Environment:
All models

Cause:
Calculating external power supply requirements

Resolution:
The ATV320 digital inputs, DI1 thru DI6, consume 7mA.  The STO input consumes 16mA.
Was this helpful?
What can we do to improve the information ?