Can the ATV320 be set to maintain running speed if the Modbus communication is lost?

Issue:
Can the ATV320 be set to maintain running speed if the Modbus communication is lost


Product Line:
ATV

 

Environment:
All

 

Cause:
Configuration

 

Resolution:
Per parameter SLL in the ATV320 Programming Manual, can be set to Fallback Speed or Speed Maintain.