How can you monitor the status of the digital inputs on the ATV630 and ATV930 Process drives?

Published date: 25 March 2019

Issue:
How can you monitor the status of the digital inputs on the ATV630 and ATV930 Process drives?

Product Line:
ATV630 and ATV930

Environment:
All 

Cause:
Wants to monitor the status of logic input DI11

Resolution:

 
Address 5202 will show the status of the logic inputs.   if you want to monitor DI11 its bit 11 of the 5202 address.
  
"IL1I
IL1R"     Bit 0:     Value of LI1.
                              Bit 1:     Value of LI2.
                              Bit 2:     Value of LI3.
                              Bit 3:     Value of LI4.
                                            
                              Bit 4:     Value of LI5
                              Bit 5:     Value of LI6
                              Bit 6:     Reserved (= 0).
                              Bit 7:     Reserved (= 0).
                                            
                              Bit 8:     Reserved (= 0).
                              Bit 9:     Reserved (= 0).
                              Bit 10:   Reserved (= 0).
                   *   Bit 11:         Value of LI11
                                            
                              Bit 12:   Value of LI12
                              Bit 13:   Value of LI13
                              Bit 14:   Value of LI14
                              Bit 15:   Value of LI15
 