How can it be verified the motor is running through the shorting contactor and not the ATS48? 

Published date: 13 November 2018

Issue: 
Validate motor is running throught the shorting contactor not the soft stater. 

Product Line:
ATS48

Environment:
All serial numbers 

Cause:
Testing the contactor 

Resolution:
Verify the r2A and r2C is closed. 
Measure motor current on the load side of the shorting contactor. 
 