Enclosed 8639 22U enclosed ATS22 soft starter is not running in Auto mode. 

Issue:
Enclosed 8639 22U enclosed ATS22 soft starter is not running in Auto mode. 

Product Line:
8639 22U enclosed ATS22

Environment:
All 

Cause:
Auto start is not starting the soft starter. 

Resolution:
Normally the auto start for auto is terminals 5-6.  So the end customer will need to close a set of dry contacts on these terminals to start the unit in Auto mode. 

You can find the basic wiring diagrams in the Enclosed Altistart 22 manual 
https://www.schneider-electric.us/en/download/document/30072-453-26/

 