What are the power losses fro ATV regen ATVRU75N4, RD15N4 ?

The power loses are :

- 12W in standby mode for the both reference
- 346W at the continous nominal power for the reference ATVRU75N4
- 381W at the continous nominal power for the reference ATVRD15N4

To determine the loses according to the braking cycle, the curve is linear (0 power = 12W and 100% of power = 346W or 381W)