Is it possible to run ATV drives with step-up transformer at the output?

Published date: 25 February 2019

Issue:
Is it possible to run ATV drives with step-up transformer at the output?
 
Product Line:
Altivar Drives
 
Environment:
All
 
Cause:
Altivar Drives with step-up tansformer
 
Resolution:
For Altivar Process it is possible to run step-up solution (ATV drive + sinus filter + step up transformer + motor). There is no special version necessary like S387 that was needed for ATV61
So we can offer ATV930/ATV950/ATV960/ATV980 with sinus filter for step-up solutions.
Required settings for transformer on the output:
[Motor Control Type] Ctt = U/f 5pts
[Sinus Filter Activation] OFI = Yes
 
For ATV machine (ATV320, ATV340) there is not such possibility. First, ATV machine offer is dedicted for machines that have limited power range and second, they the machines use standard voltage class. No sinus filter exist for ATV320/340

Contact your local Drives PAE, Product Application Engineer for further assistance with this application.