Single Line Configuration utility: The active project is not showing in the list of projects

Published date: 27 March 2019

Applies to:
PSO 8.2 and Cumulative Updates (1 through 7)

Issue:
When opening the Single Line Configuration utility the active project is not showing in the list of projects.

Causes:
If the main project is not including "PLS_Include" but a renamed copy of the original "PLS_Include", then the Single Line Configuration utility will not detect and will not add the main project into the list of projects.

Fixes:

*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

To make this work, replace the "PLS_Include" name with the new project name inside these 2 configuration files: GenieDefinitions.xml and SupportedGenies.xml.
In GenieDefinitions.xml there is originally a "Project" XML tag having "PLS_Include" as name attribute:
<?xml version="1.0" encoding="utf-8"?>
<GenieDefinitions>
  <Project name="PLS_Include">
This string has to be changed to the new included project name.

The same in SupportedGenies.xml there is originally a "Project" XML tag with "PLS_Include" name attribute:
<?xml version="1.0" encoding="UTF-8"?>
<SupportedGenies>
    <Project name="PLS_Include">
This string has to be changed to the new included project name.

 