Technical FAQs

Ask a Question

ION Setup Locked Arithmetic Modules

Issue
A user would like to edit the arithmetic modules in ION Setup, but display the error 'Attempt to access Hardware Locked module denied' when attempting to modify the module.

Product Line
PM8000
ION8650, ION8600
ION7650, ION7600, ION7550, ION7500, ION7400, ION7300 series
ION8800, ION7700


Environment
ION Setup 3.0
Advanced Mode Modules


Cause
Module's become hardware locked on ION meters

Resolution
The follow example can be applied to other modules in Advanced Mode as well. See ION Reference for detailed descriptions of the ION Modules.

Follow the steps below for a workaround to create an arithmetic module to modify:

Login to ION Setup


Under setup screens in ION Setup enter advanced mode. While holding the CTRL key, click on the device (left hand side of the screen) > all the modules in the advanced mode should appear



Navigate to the Arithmetic Module folder
Right-click in the folder (on the right hand side) then while holding the CTRL key, click on Insert Module




Enter unit password, a Create Modules window opens
Check mark an available Arithmetic module, then click Create.




Arithmetic Module (with an X going across it) will appear in the list
Double-click on the new module to edit/modify the parameters.




Note: Suggested to start from the highest module and create modules until you reach one you can edit. There are multiple reasons about how a module can become locked and you will not be able to edit them. This way you can choose a module to create and have a higher chance of being able to edit/modify the module. Please refer to ION Device Template Reference for more information regarding Module Count and Locked Modules.