Technical FAQs

Ask a Question

Is M340 SD card compatible with M580?

Question:
Is M340 SD card compatible with M580?
 
Answer:
No, the M340 and M580 SD card are not compatible. They both have special formatting required by the PLC.
The BMXRMS004GPF memory card is formatted specifically for the M580 CPUs.
NOTE:
If you insert an incompatible SD memory card in the CPU:

l The CPU remains in NO_CONF state.
l The CPU BACKUP LED turns ON.
l The memory card access LED remains OFF.


 
Was this helpful?
What can we do to improve the information ?