How can you convert the ATV312 drives program into a ATV320 drive so that the modbus address is default to address 1?

Issue:
How can you convert the ATV312 drives program into a ATV320 drive so that the modbus address is default to address 1?

Product Line:
Altivar 312 and Altivar 320

Environment:
All 

Cause:
The default modbus address on the ATV320 drive is OFF and the default modbus address on the ATV312 was 1.

Resolution:
If you convert the ATV312 drives file using Somove to a ATV320 drive files it will convert the modbus address to default 1.