What are default values of stator resistance, inductance RSA, LFA, TRA in ATV320 ?

There are no default values of RSA, LFA, TRA in the drive. These values depends on motor data that are entered. NPR, ULN, NCR, NSP
As soon as you enter these data, values RSA, LFA, TRA will be changed. These changed values will be considered by motor control algorithm unless autotuning is executed.
Autotuning will overwrite RSA. LFA, TRA.