Can the relays and digital outputs on the Process ATV600 / ATV900 series be controlled over the network?

 Issue:
Can the relays and digital outputs on the Process ATV600 / ATV900 series be controlled over the network?

Product Line:
Process ATV600 ATV900

Environment:
All models

Cause:
NA

Resolution:
Yes.
The relays ( R1 / R2 / R3... ) and digital outputs ( DO1 / DO2... ) can be controlled from the network by writing to address 5212.  The relay or digital output assignment needs to be set to "Not Assigned".  If it is assigned to a function, then the network write on the corresponding bit will not affect it.