Can you program Jog Forward and Jog Reverse on the Altivar 630 and Altivar 930?

Published date: 18 December 2018

Issue:
Can you program Jog Forward and Jog Reverse on the Altivar 630 and Altivar 930?

Product Line:
Process Drive ATV630 ATV930

Environment:
All

Cause:
Application

Resolution:
you will need to wire and program per listed parameters below:

Under Complete Settings : 
1. In the Command and Reference Menu > Reverse Disable = NO
...By Default in 2 Wire Control DI1 is Run Forward
   **(note: by default DI2 is your Reverse Input)

2. In the Generic Functions Menu > JOG > JOG=DI5, JGF=10hz

When you enable DI1 and DI5 the motor will run forward at 10hz, when you enable DI2 and DI5 with DI1 Low, the motor will run reverse at 10hz.  Always Stop by releasing DI1 or DI2 prior to switching directions.