Browse FAQs

Can an ATV212 logic input be programmed as both a run command and a preset speed?

Published date: 30 October 2018

Issue:
ATV212 can you program a run enable and preset speed on the same input?

Product Line:
S-Flex ATV212

Environment:
All 

Cause:
Set up Run and Preset speed at the same time. 

Resolution:
Yes.  The logic inputs have options for combination assignments.

22 = run forward + preset speed 1
23 = run reverse + preset speed 1

Eg:  Logic input F assignment F111 = 22
Input OFF - Motor stops
Input ON - Motor runs forward at speed set by Sr1 (preset speed 1)

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.