Opening an '.sta' file for a CanOpen application returns the error 'The required application object reference...CanOpen_Option_Default ... signature is different'

Goals and Symptoms
Opening an '.sta' file for a CanOpen application returns the error 'The required application object reference...CanOpen_Option_Default ... SIGNATURE is different' 

Facts and Change
Unity

Causes and Fixes
After importing the '.eds' file for a CanOpen deivce into the Hardware Catalog and opening an '.sta' file for a CanOpen application returns
the error 'The required application object reference <...CanOpen_Option_Default ...> signature is different'.





The following steps can be used to resolve the issue:.
  • Open the Hardware Catalog Manager
  • Delete the third party device.  This will delete '.eds' file from the catalog.



 
  • Build the Hardware Catalog
  • Open the '.sta' file.
 
Note: Opening of the '.sta' file by Unity Pro automatically updates the Hardware catalog including the equipment with the
correct signature.    

 
Was this helpful?
What can we do to improve the information ?