ATS22 stops whent he start button is released?

Issue:
Softstart stops when the start button is released?

Product Line: 
MCC

Enviroment:
8639 22U

Cause: 
ATS22  stops whent he start button is released

Resolution:
Verify 2 wire / 3 wire control  wiring configuration is correctly wired to the softstart. 
Verify control circuit has no loose or open connections.
Verify RCR relay connections and operation.
Verify the latching circuit in the control wiring is being maintained to hold the run command. 




 