What is the Max Torque Angle for 32R protection for a MiCOM P343
Issue What is the Max Torque Angle for the 32R power protection for a MiCOM P343
Product Line
MiCOM P343
Environment
Relay Protection Settings
Resolution
There is no Max Torque Angle for the 32R power protection. The element measures the 3 phase power based on the equation stated in the operation chapter in the P343 manual so there is no setting for the Max Torque Angle. The directional criteria for the power flow is either forward or reverse.