Can you power up the ATV32 with an external 24Vdc supply?

Issue
Can you power up the ATV32 with an external 24Vdc supply?

Product Line:
ATV32 

Environment:
All serial numbers

Cause:
To maintain control power to the drive. 

Resolution: 
Yes, the P24 terminal and COM are the connections that can be used for external 24VDC. 
  **NOTE:  This does not apply to the ATV320, the P24 terminal on ATV320 is only used to supply the STO (Safe Torque Off) terminal, P24 will not accept 24v.