What is the difference between ACC and tLS when configuring ATS22 soft starter?

Issue:
What is the difference between ACC and tLS when configuring Altistart 22 

Product Line:
Altistart 22 ATS22

Environment: 
All

Cause: 
There 2 different settings for the acceleration ramp time.

Resolution:
ACC [acceleration] = time to ramp from 0 to 60hz when a run command is given. The full inrush of the motor has to drop at the end of the ACC Ramp, before the motor is dropped to the shorting contactor.   tLS [Max Start Time]  is time to ramp from 0 until the motor is dropped out to the internal shorting contactor, thus has to be longer than ACC.