How to transfer programs from on ATV630/930 series drive to another with the VW3A11111 graphics keypad?

Issue:
How to transfer programs from on ATV630/930 series drive to another with the VW3A11111 graphics keypad?

Product Line:
Altivar 630/930

Environment:
All

Cause:
N/A

Resolution:
From main menu go into menu 7 File management.
Enter on 7.1 Transfer config file.
2 options:
Copy to the drive from keypad.
Copy from the drive to the keypad.
When the program is copied from the drive to keypad the drive gives you the option to naming the file to what ever you want. 
Enter to continue.

Downloading from the keypad to the drive is similar.
The drive will prompt you to choose which file you want to use so it is important to remember what the name of the file you saved into prior.
When transferring programs the drives part number and firmware version will have to match.  Otherwise you will get a configuration error.