What are possible causes for DB Unit Short Circuit Fault on ATV930 drive?

Published date: 20 November 2018

Issue:
What are possible causes for DB Unit Short Circuit Fault on ATV930 drive?

Product Line:
ATV930, Altivar 930

Environment:
All

Cause:
NA

Resolution:
The fault may occur if  DB Transistor is shorted. Perform a diode check across PA to PB to check if Transistor is shorted. Also, check BrA is set to Yes.