Technical FAQs

Ask a Question

What is rated impulse withstand voltage (Uimp) for ATV process?

ATV process product datasheet decleares under electromagnetic compatibility that it complies Electrical fast transient/burst immunity test level 4 according to IEC 61000-4-4
In this standard, the peak value of the voltage for level 4 is 4kV, see table in attachment. From this reason ATV process must withstand impulse voltage of 4kV.
Conditions for reated impulse withstand test as well as parameter of the impulse are specified in this standard IEC61000-4-4.  
Was this helpful?
What can we do to improve the information ?