How to connect braking resistor to ATV340, 11kW drive ?

Published date: 19 March 2019

Issue:
How to connect braking resistor to ATV340, 11kW drive ?

Product Line:
Altivar ATV340

Environment:
All

Cause:
N/A

Resolution:
For ATV340 smaller sizes (size 1 and size 2), there are terminals PB and PBe on CN10 connector for connecting braking resistor
Size 1 and 2 are ATV340 drives up to U75N4 included


On ATV340 size 3 and larger, braking resistor must be connected to PA/+ and PB. See attached picture.
Size 3 and larger = ATV340D11N4 and above