ATV71 : What cause a INF2 fault on the ATV71 drive

Issue: 
What causes an INF2 fault on the ATV71 drive? 

Product Line:
ATV71

Environment:
All products

Cause: 
The Drive trips in INF2 fault when the software version is incompatible with the application and control motor boards. 

Resolution:  
Check the reference of the power board and its compatibility.  Re-flash the control board or replace it.  Reseat the power card and control card, and try to power cycle the drive.

 