What are the conditions for residual current devices discrimination?

2 conditions have to be fulfilled for RCD discrimination:
- current discrimination: IΔn upstream RCD > 3 x IΔn downstream RCD
- time discrimination: minimum non-tripping time of upstream RCD > maximum tripping time of downstream RCD.
 