What are the limits on setting up the password on the ATV630 Process drive?

Issue:
What are the limits on setting up the password on the ATV630 Process drive?

Product Line:
ATV630

Environment:
All 

Cause:
password features 

Resolution:
The menu [8.2 Password] is only regarding the possibility to download/upload configuration. The menu [8.3 Parameter Access] let the possibility to modify the visibility of all or list of parameters from HMI or communication channels. It will hide the parameter but even if the password is set, the visibility can be modify because the menu 8.3 is still accessible even if a password is configured. We ask an evolution to the firmware to be able to hide or not parameter and to avoid modification of all or partial configuration with a password. 